![]() having problems connecting the dosing pumps.
i have to power bars that are daisy changed out of s1-4. i have connected the dosing pump to the end of the last power bar. also gone to the socket functions and programe digital power bar and dosing pump. dosing pump numbers selected as 1-4 as i have a 4 dosing pump unit. after all this the dosing pumps stay on. i cant turn them off. any ideas? any chance that we can copy and paste the screen shots so we can post post them on the forum. |
#2
|
||||
|
||||
![]() reef,
regarding dosing pump. Your pumps have numbers 1,2,3,4, correct? And your powerbar has some numbers above, for example 5-10? If you use the manual override can you activate each dosing pump and socket as expected? (the pumps react when you activate a socket with number 1-4, the sockets react when you activate sockets 5-10 in ProfiLuxCOntrol) |
#3
|
||||
|
||||
![]() i just found this which helped
http://www.ghl-kl.de/Produkte/Aquari...DosingPump.pdf Quote:
can i put them after the last power bar, so say 13-16? if i put the dosing pumps on 1-4 then it i have to change all my existing sockets and timers. |
#4
|
||||
|
||||
![]() "Do they have to be 1-4?" - No, you can assign any numbers for digital powerbars and dosing units you want.
"can i put them after the last power bar, so say 13-16?" - yes Hint: With firmware 3.05 you can program powerbars and dosing units (startnumer or initial state) with ProfiLuxControl 3.0.5.0 |
#5
|
||||
|
||||
![]() Thanks again Matthias,
Perfect, i got the dosing pumps going. So when i select 24 dosings per day for pump one, will it dose every hour? Last edited by reef; 11-17-2007 at 10:15 AM. |
#6
|
||||
|
||||
![]() Exactly!
|
#7
|
|||||
|
|||||
![]() Excuse my ignorance but what is an SSID and how do I find out what mine is?
|