Sorry Michael, Have another one for you
I picked up a new temp probe and it has been working perfectly. Today I added the extention cable to the temp probe.
Without the extension temp was reading 79.4
I followed the extension cable instruction as per the latest operator instructions.
1)entered the extension mode without the extesion cable attached (probe was in the tank in the same spot it would be when the cable gets added)
2)press return and wait
3) controller say Change
4) add the extension cable and press return
5) wait and then save
My temp was then reading 74.2
in order to correct this I calibrated the sensor with the extension cable and the temp control returned to 79.5
Have I performed the procedure incorrectly?
Thanks
Jason
|